Gas Fire Extinguishing Systems
Suspended HFC-227ea gas fire extinguishing device composed of agent storage bottle, container valve, electromagnetic driving device, nozzle, temperature-sensing glass ball, pressure feedback device and suspension bracket. Hanging installation — no agent pipeline and no dedicated bottle room required.
| Model | XQQCW10/1.6-ZHTA / XQQCW20/1.6- ZHTA / XQQCW30/1.6-ZHTA |
|---|---|
| Agent filling capacity | 10kg / 20kg / 30kg |
| Storage pressure | 1.6MPa(20℃) |
| Maximum working pressure | 2.5MPa(50℃) |
| Filling density | ≤1120kg/m³ |
| Extinguishing technique | Total flooding |
| Agent discharge time | ≤10S |
| Starting mode | Fixed-temperature glass bulb (68 °C) / DC24V solenoid start |
| Operating ambient temperature | 0℃~50℃ |
Send us your protection requirements and our engineers will propose a configuration.
Request a Technical Proposal