Non-pressurized pre-engineered unit for battery packs

Gas Fire Extinguishing Systems

Non-pressurized pre-engineered unit for battery packs

Product Overview

Stored-pressure pre-engineered perfluorohexanone fire extinguishing device. Installed in small spaces such as battery packs and distribution cabinets, independently packaged without external pipelines. No heat or fire source is generated during detection and discharge, reducing combustion risk.

Key features

  • When ambient temperature reaches 68 °C the thermosensitive glass bulb breaks and the agent is sprayed
  • No heat or ignition source in detection or discharge
  • Compact one-piece construction, quick installation
  • Clean agent, harmless to equipment and environment

Download Datasheet (PDF) Ask About This Product

Product Parameters

ModelYF0.2/1.2-ZHTA
Extinguishing agentFK-5-1-12 (perfluorohexanone)
Agent quantity (g)160
Storage pressure1.2MPa
Activation condition68℃±3℃
Operating ambient temperature-10℃~+50℃
Overall dimensions (L×W×H)140*125*20mm