Gas Detection & Industrial
Built on zero-point calibration technology, the GTYQ-ZH uses a catalytic combustion sensing principle to continuously detect combustible gas concentrations in the ambient environment. It is fitted with imported high-quality gas-sensitive elements for accurate detection, fast response and stable temperature/humidity characteristics.
| Detection principle | Catalytic combustion / Humidity range |
|---|---|
| Detectable gases | Rated power / 0.9 W standby / 1.5 W alarm (incl. sounder) |
| Drift | Zero drift < 3 %/year, span drift < 5 %/year / Ingress protection / IP65 |
| Repeatability | ±3%F.S. / Explosion-proof marking / Ex d IIC T4 Gb / Ex tb IIIC T130 °C Db |
| Working voltage | 24VDC / Alarm settings / 25 %LEL (low) / 50 %LEL (high) |
| Measuring accuracy | ±3 %LEL / 3 %LEL – 100 %LEL |
| Housing material | Cast aluminium / Low-level output / 24V/100mA |
| Operating temperature | -40~+60℃ / High-level output / 24V/1A |
| Storage temperature | -40~+60℃ / Communication / RS485 / CAN bus |
| Sensor service life | Electrochemical ≥ 2 years (depends on environment) / Display / High-brightness digital display |
| Response time | ≤25S |
Send us your protection requirements and our engineers will propose a configuration.
Request a Technical Proposal